Six actions, four governing combinations and five mistakes that keep recurring in carport designs. A design-side walkthrough against EN 1990, EN 1991-1-1, EN 1991-1-3, EN 1991-1-4, EN 1993 and EN 1090-2.
Short answer. A solar carport is sized by listing the actions first, not by picking a section: permanent action from modules and steel, roof imposed load, snow, wind uplift, seismic where relevant, plus construction, maintenance and ponding. Characteristic values come from EN 1991; the design values from EN 1990 with γG = 1.35 (unfavourable) and γQ = 1.5. Open carports are usually governed by wind uplift, and the wind coefficients must be taken from EN 1991-1-4 §7.3 (canopy roofs, net pressure coefficients cp,net), never from the external coefficients used for enclosed buildings.

Contents
- 1. Start with an action schedule, not a formula
- 2. Permanent action: use the module datasheet, not a rule of thumb
- 3. Roof imposed load: 0.4 kN/m² plus a 1.0 kN point load
- 4. Snow: μ1 = 0.8, and why low-pitch carports keep it
- 5. Wind: the governing case, and §7.3 canopy roofs
- 6. Seismic, ponding and thermal
- 7. Combinations: four cases, and uplift is not a member check
- 8. From actions to sections: four checks that actually decide the design
- 9. A worked purlin example
- 10. Five mistakes that keep coming back
- 11. What we need to produce a reviewable calculation
- Preguntas Frecuentes
- Regional differences that change the answer
- References
1. Start with an action schedule, not a formula
Most carport errors are omissions rather than arithmetic. Build the schedule before opening a calculation sheet.
Table 1. Actions on a solar carport and where the values come from
| Action | How the value is set | Clause | What gets missed |
|---|---|---|---|
| Permanent action G | Module mass from the datasheet, steel from section weights | EN 1991-1-1 §4 and Annex A | Often missed: connectors, gutters, edge flashing, lighting trays, EV chargers |
| Roof imposed load Q | qk = 0.4 kN/m² with Qk = 1.0 kN, category H | EN 1991-1-1 Table 6.9 and Table 6.10 | Check the National Annex, which may set different values |
| Snow S | s = μi · Ce · Ct · sk | EN 1991-1-3 §5 | Low pitch, obstruction at the eaves, drift at parapets |
| Wind W | cp,net and cf for canopy roofs | EN 1991-1-4 §7.3, Tables 7.6 to 7.8 | Obstruction factor φ, the lower surface, edge zones A/B/C |
| Seismic | Where the site and client require it | EN 1998, National Annex | Anchor and base plate design |
| Other | Ponding, thermal movement, vehicle impact, ice | Project specification | Blocked drainage, low points, bollards at columns |
2. Permanent action: use the module datasheet, not a rule of thumb
Module load is mass divided by outline area, not a number of kilograms per panel. Current bifacial frameless modules work out around 12–13 kg/m², but two 550 W modules of different formats can differ by more than 10 % in area load. A module change without re-running the permanent action is the most common single point of failure at the start of a carport design.
Steel is summed from section weights: C and Z purlins, RHS or H columns, rails. Allow 3–5 % for connectors and fasteners, and add gutters, edge trim and cable trays as line loads. EV chargers, battery cabinets and lighting masts are point loads at their actual positions, not smeared into the roof load.
Convert the result into a purlin line load q = g × purlin spacing. Everything downstream depends on this one step being right.
3. Roof imposed load: 0.4 kN/m² plus a 1.0 kN point load
For a roof accessible only for normal maintenance and repair, category H, EN 1991-1-1 Table 6.10 gives the recommended values qk = 0.4 kN/m² and Qk = 1.0 kN, applied separately. The National Annex may vary both, and may vary qk with roof slope, so the NA has to be checked before the value is fixed.
The two values do different jobs. The distributed load covers temporary storage and maintenance activity across an area; the point load covers a single foot or a tool box on the purlin mid-span, at a cleat, or at the eaves. A purlin that passes the distributed case can still fail the point load case at mid-span.
EN 1991-1-1 §3.3 also states that roof imposed loads, particularly for category H roofs, need not be applied in combination with snow or wind. In EN 1990 terms the combination value ψ0 for category H is 0, so roof imposed load never becomes an accompanying action. That is a simplification, not a licence to ignore it: projects with maintenance access during the snow season, or with cleaning robots and walkways, need the real access load modelled.
4. Snow: μ1 = 0.8, and why low-pitch carports keep it
Snow on the roof is s = μi · Ce · Ct · sk, with sk taken from the National Annex snow map for the site. Ce and Ct are normally 1.0 for an unheated open structure.
For monopitch roofs, EN 1991-1-3 Table 5.2 gives μ1 = 0.8 for 0° ≤ α ≤ 30°, reducing to 0 at 60°. Most carports sit between 5° and 15°, so the full 0.8 applies. The standard also requires μ1 not to be reduced below 0.8 where sliding is obstructed, for example by snow fences, a parapet at the lower edge, or modules laid with gaps that retain snow.
Drift matters as much as the balanced load. Snow sliding off a low-pitch carport piles up at the eaves and around column bases; parapets and adjacent taller buildings create local drift, which EN 1991-1-3 §6 treats separately. Check the eave purlin and gutter for the drifted case, not just the uniform one.
5. Wind: the governing case, and §7.3 canopy roofs
Peak velocity pressure qp(ze) comes from the basic wind velocity in the National Annex, terrain category and orography. For a carport under 15 m, cs cd = 1.0 is normally acceptable, and small structures of this type do not need a dynamic response analysis.
The coefficient is where carport designs go wrong. A carport with no permanent side walls is a canopy roof in the sense of EN 1991-1-4 §7.3, not an enclosed building under §7.2. Section 7.3 works with net pressure coefficients cp,net over zones A, B and C, and with an overall force coefficient cf, because wind acts on the upper and lower surfaces at once. Using the §7.2 external coefficients on an open canopy is wrong in both directions: too conservative in the middle of the roof, and unconservative at the edges.
Three details in §7.3 decide the result:
- Obstruction factor φ. φ = 0 for an empty canopy, φ = 1 for a canopy fully blocked below. A carport with parked vehicles is somewhere in between and the tables are interpolated, which is why the same canopy can carry visibly different coefficients in summer and winter conditions.
- Zone split. Zones A, B and C carry different cp,net, and the edge and corner zones produce the highest local suction. Purlins, clamps and fasteners are checked against the local zone value, not an average over the roof.
- Eccentricity. The resultant wind force acts at d/4 from the windward edge, which imposes a torsional or eccentric effect on the supporting structure. A single central column row or a cantilevered canopy absorbs this, and it is frequently omitted when a carport is modelled as a simple uniformly loaded beam.
Directionality and array effects also matter. In a row of carports the first and last rows see different pressures from the interior rows, and the end bays differ from the middle bays. Take the unfavourable value per position instead of one value for the whole array.
For the record, the qualitative behaviour is confirmed by measurement as well as by the standard. A rigid-model pressure study on monopitch solar carports at 10°, 20° and 30° (Li Shouke et al., Journal of Vibration and Shock, 2019) found suction dominant on the upper roof area and pressure dominant on the lower area, with the worst suction at the upper eave corner and the worst pressure at the lower eave corner. The measured worst overall load was about 20 % below the value obtained by treating the canopy as an enclosed building, while parked vehicles increased the worst mean suction on the upper area by about 10 %. Both directions of error appear in the same study.
6. Seismic, ponding and thermal
Seismic action is rarely governing for a light carport, but base plates, anchors and module clamps still have to be designed for the site’s seismic action where EN 1998 applies. Ponding is the more common practical issue: a blocked gutter or a low point in the roof turns 100 mm of water into 1.0 kN/m² of additional load, enough to change which case governs the purlin. Thermal movement needs joints on long canopies, and columns on a vehicle route need impact protection as a design decision, not an afterthought.
7. Combinations: four cases, and uplift is not a member check
Table 2. Governing combinations for a carport
| Combination | Expression | What it governs |
|---|---|---|
| ULS, wind leading (STR) | 1.35 G + 1.5 W + 1.5 × 0.6 S | Rafters, columns, purlins, stability |
| ULS, snow leading (STR) | 1.35 G + 1.5 S + 1.5 × 0.6 W | Purlins, eave, gutter |
| Static equilibrium, uplift (EQU) | 0.9 G + 1.5 W | Overturning, anchor pull-out, foundation uplift |
| Serviceability (SLS) | G + W + 0.6 S, γ = 1.0 | Purlin deflection, column head displacement |
The partial factors come from EN 1990 Table A1.2(B) for STR/GEO, with γG,sup = 1.35, γG,inf = 1.0 and γQ = 1.5. Equilibrium verification follows Table A1.2(A), where γG,sup = 1.10 and γG,inf = 0.90. The distinction matters: a purlin is checked under STR with 1.35 G against 1.5 W, while the base plate and anchor are checked under EQU with 0.9 G against 1.5 W, and the second case is the more onerous one for hold-down.
Combination values are from EN 1990 Table A1.1, with ψ0 = 0.6 for wind, ψ0 = 0.5 for snow at altitudes below 1000 m outside Finland, Iceland, Norway and Sweden, and ψ0 = 0 for category H roofs. These are recommended values and every National Annex may change them, so the NA of the project country takes precedence over the main text.
8. From actions to sections: four checks that actually decide the design
Purlin. Line load from area load times spacing, simply supported or continuous, bending plus deflection. Under uplift the bottom flange is in tension and the top flange in compression, and a cold-formed lipped channel is far less stable in that direction than under downward load. A purlin chosen only for gravity load can pass the snow case and fail the wind case.
Rafter and column. Wind uplift can put a column into tension rather than compression. Base plates, anchor bolts and column-to-rafter connections are designed for that tensile force, and the calculation should show it explicitly rather than assume compression throughout.
Base plate and foundation. Overturning, sliding and uplift are verified together, with the foundation designed to EN 1997-1 and, where applicable, EN 1993-1-8 for the connection. Anchor pull-out capacity in cracked concrete, edge distance and grout thickness decide the real capacity far more often than the plate bending check.
Fixings and clamps. Module clamps, self-drilling screws, purlin-to-rafter screws and rail connectors are checked against the local peak pressure of the edge zone. This is the first item to fail on site after a storm, and the hardest to attribute afterwards.
9. A worked purlin example
The numbers below are illustrative only. Use the site-specific wind and snow values, zone coefficients and National Annex parameters in a real project.
Assumptions: purlin spacing 1.2 m, span 4.0 m simply supported, permanent load 0.28 kN/m², snow 0.28 kN/m², wind uplift 0.50 kN/m². Line loads: g = 0.34 kN/m, s = 0.34 kN/m, w = 0.60 kN/m upwards.
Gravity, snow leading: 1.35 × 0.34 + 1.5 × 0.34 = 0.97 kN/m, M = 0.97 × 4²/8 = 1.94 kN·m.
Uplift, STR, wind leading: 1.35 × 0.34 − 1.5 × 0.60 = −0.44 kN/m, M = 0.44 × 4²/8 = 0.88 kN·m, bottom flange in tension.
Uplift, EQU, for the hold-down: 0.9 × 0.34 − 1.5 × 0.60 = −0.59 kN/m, equivalent bending 1.19 kN·m, and an uplift reaction to be carried by the anchor.
The point of the example is the direction. For the same purlin, the check that usually governs is not snow pushing down but wind pulling up, and the check that governs the foundation is the third case, not the first.
10. Five mistakes that keep coming back
Table 3. Recurring errors and their consequences
| Recurring error | Consequence |
|---|---|
| Using §7.2 external coefficients for an open canopy | Middle of the roof over-designed, edges and fixings under-designed |
| Taking φ = 0 regardless of parked vehicles or stored goods | Suction under-estimated exactly where vehicles sit |
| Ignoring the d/4 eccentricity of the wind resultant | Central columns and cantilever canopies under-designed for torsion |
| Sizing only for downward load | Column tension, anchor pull-out and foundation uplift missed |
| Letting roof imposed load accompany snow and wind | Load case combination wrong; ψ0 = 0 for category H is not applied |
11. What we need to produce a reviewable calculation
Table 4. Inputs for a carport load calculation
| Input | What to supply |
|---|---|
| Site location | National Annex basic wind velocity and ground snow load |
| Terrain category and orography | Terrain category 0 to IV, local topography factor |
| Geometry | Span, bay spacing, eave and ridge height, pitch, number of rows, side walls and cladding |
| Module data | Type, dimensions, mass, portrait or landscape layout |
| Structure | Column type, purlin and rafter sections, steel grade, corrosion protection |
| Foundation | Pad, strip or ground screw, groundwater and soil parameters |
| Ancillary loads | EV chargers, battery cabinets, lighting, gutters, cleaning equipment |
| Design basis | Country National Annex, client specification, execution class to EN 1090-2, third-party review requirement |
Preguntas Frecuentes
Which standards apply to a solar carport? EN 1990 for combinations, EN 1991-1-1 for imposed load, EN 1991-1-3 for snow, EN 1991-1-4 for wind, EN 1993-1-1 and EN 1993-1-3 for the steel, EN 1090-2 for execution, EN 1997-1 for foundations, with the National Annex of the project country overriding the recommended values.
Is the roof imposed load 0.4 kN/m² or 0.5 kN/m²? Under EN 1991-1-1 the recommended category H value is 0.4 kN/m² with a 1.0 kN point load; some National Annexes and client specifications set different values. 0.5 kN/m² belongs to the Chinese GB system and should not be mixed into a Eurocode calculation.
Can a carport be treated as an enclosed building for wind? No. Without permanent side walls it falls under EN 1991-1-4 §7.3 canopy roofs, where cp,net depends on the zone and on the obstruction factor φ below the roof.
What is the obstruction factor φ? The ratio of obstructed area below the canopy to the free cross-section, from 0 for an empty canopy to 1 for a fully blocked one. Tables 7.6 to 7.8 are interpolated between the two, so parked vehicles genuinely change the design load.
Does snow load change with module pitch? Yes. μ1 = 0.8 from 0° to 30°, then reducing to 0 at 60°, and it must not be reduced below 0.8 where snow cannot slide off, for example at parapets or snow guards.
Why check the base plate for uplift when the canopy is heavy? Because the favourable permanent factor is 0.9 in the EQU combination while the wind factor is 1.5. For a light canopy the net effect can be upward, and the anchor then carries tension rather than bearing.
Do carports need a dynamic wind analysis? Generally not. For structures below about 15 m with cs cd = 1.0 the quasi-static approach is adequate; the exception is unusual geometry or a site with strong orographic effects.
Does corrosion change the load calculation? It changes the resistance, not the load. Under EN ISO 12944 corrosivity categories C4 and C5, section loss and coating mass have to be allowed for, which is why a coastal carport needs a heavier zinc coating than an inland one for the same span.
Regional differences that change the answer
In the GCC and wider Middle East, snow drops out and wind plus ponding from blocked drainage governs; coastal sites sit in the lowest terrain categories, so qp(ze) rises quickly. In northern and central Europe, snow governs purlins at low pitch and drifting at parapets becomes the local check. On any coastline, whether in the Gulf, the Red Sea or the North Sea, the corrosion category sets how much section is left to carry the calculated force, so load and durability have to be specified together.
References
- EN 1990:2002+A1:2005, Eurocode 0, Basis of structural design, Tables A1.1, A1.2(A) and A1.2(B)
- EN 1991-1-1:2002, Eurocode 1, Part 1-1, Tables 6.9 and 6.10 and §3.3
- EN 1991-1-3:2003+A1:2015, Eurocode 1, Part 1-3, §5.3 Table 5.2 and §6
- EN 1991-1-4:2005+A1:2010, Eurocode 1, Part 1-4, §7.3 canopy roofs, Tables 7.6 to 7.8
- EN 1993-1-1:2005 and EN 1993-1-3:2006, steel and cold-formed steel design
- EN 1090-2:2018, execution of steel structures
- EN 1997-1:2004, geotechnical design
- EN ISO 12944, corrosivity classification and protective paint systems
- Li Shouke, Liu Zhiyu, Zhang Xue, Fang Xianglu, Gao Wenjing, Sun Hongxin, Wind tunnel study of monopitch solar carports, Journal of Vibration and Shock, 2019